Sonic-alert Digital Program Controller DCP301 Uživatelský manuál Strana 49

  • Stažení
  • Přidat do mých příruček
  • Tisk
  • Strana
    / 187
  • Tabulka s obsahem
  • ŘEŠENÍ PROBLÉMŮ
  • KNIHY
  • Hodnocené. / 5. Na základě hodnocení zákazníků
Zobrazit stránku 48
Chapter 4. WIRING
4-17
5-wire system RS-485 mutual connection
57
58
59
60
61
SDA
SDB
RDA
RDB
SG
FG
57
58
59
60
61
SDA
SDB
RDA
RDB
RDA
RDB
SDA
SDB
SG
FG
SG
FG
57
58
59
60
61
SDA
SDB
RDA
RDB
SG
FG
Terminating resistor
Terminating resistor
Terminating resistor
Terminating resistor
Slave station DCP301
Shielded cable
Shielded cable
Shielded cable
Master station
Slave station DCP301
Slave station DCP301
Provide terminating resistor of 150Ω±5%, 1/2W min. at both ends of the communications path.
Grounding of the shielded FG terminal should be carried out at only one end and not both ends.
Be sure to connect SG terminals each
others.
Failure to do so might cause unstable
communications.
Handling Precautions
Zobrazit stránku 48
1 2 ... 44 45 46 47 48 49 50 51 52 53 54 ... 186 187

Komentáře k této Příručce

Žádné komentáře