Chapter 7. PARAMETER SETUP
7-9
No. Item Code Item Factory User Setting
Setting Setting
29 M .-C 0
30 M .-A T 0
31 M .-C L 1000
32 M .-O P 9000
33 M .-T 30.0
0: MFB control (conventional) + estimated position
control
1: MFB control (conventional) only
2: Estimated position control only
[Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible.
0: Adjustment disabled
1: Adjustment enabled
[Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible.
On 2G output models, when M .-C setting is 2, “– – – –
” is displayed and setting is not possible.
0 to (fully open adjustment - 500)
[Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible.
On 2G output models, when M .-C setting is 2, “– – – –
” is displayed and setting is not possible.
(fully closed adjustment + 500) to 9999
[Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible.
On 2G output models, when M .-C setting is 2, “– – – –
” is displayed and setting is not possible.
5.0 to 240.0s
[Note]
On models other than 2G output models, “– – – –” is
displayed and setting is not possible.
Motor control
method selection
Motor valve opening
automatic adjust-
ment
Motor valve opening
adjustment fully
closed position
Motor valve opening
adjustment fully
open position
Motor valve opening
adjustment fully
open/closed time